6
OPERATION
106
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
For more data about the menu items, refer to
Function description
on page 77
–
table C. Full
Setup menu.
Figure 6-8: Level measurement
1
Tank Height (C1.2)
2
Tank bottom reference point. You can use menu item C1.11 Tank Bottom Offset to move the position of the tank bottom
reference point.
3
Blocking Distance (C1.5)
4
100% Range (C4.1.3), if menu item C4.1.4 Current Out. Range is set to "4-20mA" or "3.8-20.5mA"
5
0% Range (C4.1.2), if menu item C4.1.4 Current Out. Range is set to "4-20mA" or "3.8-20.5mA"
6
Non-measurement zone
Bar graph function in Normal mode
Bar graph function in Normal mode
Bar graph function in Normal mode
Bar graph function in Normal mode
There is an optional bar graph shown on the two measurement pages in Normal mode (set
C6.4.1 / C6.5.1 (Function) to "One Value & Bar" or "Two Values & Bar"). By default, the bar graph
on the 1st Measurement Page shows a value related to the measurement scale specified in the
C4.1 Current output 1 menu. It is possible to give different measurement scales and
measurement variables for the bar graphs in Normal mode. For more data, refer to Function
description on page 77
–
table C. Full Setup menu (C6 Display). The bar graph range is related to
the parameters given in the menu item C6.4.2 and C6.5.2 (1st Value Variable) and menu C1
Install. Parameters.
If you change C1.11 Tank Bottom Offset, then we recommend that you change C6.4.3 / C6.5.3 (0%
Range) and C6.4.4 / C6.5.4 (100% Range) by the same quantity.
www.hawkmeasurement.com
Содержание Senator S24S
Страница 173: ...NOTES 11 173 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Страница 174: ...11 NOTES 174 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Страница 175: ...NOTES 11 175 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...