OPERATION
6
99
Senator S24S
01/2019 - Senator S24S Radar Manual v1.00 en
•
[>>>>] to change the position of the
cursor.
•
[
] to decrease the value (or move
the decimal point one digit to the
left) or [
] to increase the value (or
move the decimal point one digit to
the right).
•
[
^
^
^
^
] to confirm.
100% range. Use this step to give the 100%
output setting in the tank. Refer to the
illustrations that follow. Illustration
1
shows the settings for level. Illustration
2
shows the settings for distance.
Refer to the illustrations that follow. When
menu item A4.1.3.1 Current Out. 1 Var.
A4.1.3.1 Current Out. 1 Var.
A4.1.3.1 Current Out. 1 Var.
A4.1.3.1 Current Out. 1 Var. is
set to "Level", illustration
1
shows the
position of 100% output as a level above the
tank bottom. When menu item A4.1.3.1
A4.1.3.1
A4.1.3.1
A4.1.3.1
Current Out. 1 Var.
Current Out. 1 Var.
Current Out. 1 Var.
Current Out. 1 Var. is set to "Distance",
illustration
2
shows the position of 100%
output as a distance below the flange facing
or thread stop of the process connection.
•
[
] or [
] for the selection of the
current output range (3.8-20.5 mA
(NAMUR), 4-20 mA, 3.8-20.5 mA
(reversed) or 4-20 mA (reversed).
•
[
^
^
^
^
] to confirm.
Current output range. This menu item gives
current output values to the measuring
range between 0% and 100% values given in
the "0% range" and "100% range" steps.
If you set this menu item to "4-20 mA" or
"3.8-20.5 mA":
•
0% Range = 4 mA
•
100% Range = 20 mA
If you set this menu item to "4-20 mA
(reversed)" or "3.8-20.5 mA (reversed)":
•
0% Range = 20 mA
•
100% Range = 4 mA
•
[
] or [
] for the selection of the
error function (Off, Hold, High or
Low).
•
[
^
^
^
^
] to confirm.
Error Function. This sets the behaviour of
current output 1 if an error occurs.
If this menu item is set to "Off", no signal is
given (this parameter is not available if
menu item C4.1.4 is set to "3.8-20.5 mA"
(NAMUR) or "3.8-20.5 mA (reversed)"). If
this menu item is set to "Hold", the output
current stays at the value where the error
occurred (this parameter is not available if
menu item C4.1.4 is set to "3.8-20.5 mA"
(NAMUR) or "3.8-20.5 mA (reversed)"). If
this menu item is set to "Low", the output
current changes to 3.5 mA (default value) if
an error occurs. If this menu item is set to
"High", the output current changes to
21.5 mA (default value) if an error occurs.
•
3 × [
^
^
^
^
] to confirm.
•
[
] or [
] for the selection of the
save option (Yes, No or Back).
•
[
^
^
^
^
] to confirm.
Save Configuration?
Save Configuration?
Save Configuration?
Save Configuration? screen.
Set to "Yes" to save and use the settings
and data and go back to Normal mode. Set
to "No" to cancel the changes to the device
settings and go back to Normal mode. Set
to "Back" to stay in Program mode.
Screen
Steps
Description
www.hawkmeasurement.com
Содержание Senator S24S
Страница 173: ...NOTES 11 173 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Страница 174: ...11 NOTES 174 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...
Страница 175: ...NOTES 11 175 Senator S24S 01 2019 Senator S24S Radar Manual v1 00 en www hawkmeasurement com...