179
Profile Name Character 1
82
52
The ASCII codes equivalent to each of the
16 characters of the profile name, e.g.:
A = 65dec / 0x41, B = 66dec / 0x42 etc.
a = 97dec / 0x61, b = 98dec / 0x62 etc.
Profile Name Character 2
A/R
A/R
Profile Name Character 3
A/R
A/R
Profile Name Character 4
A/R
A/R
Profile Name Character 5
A/R
A/R
Profile Name Character 6
A/R
A/R
Profile Name Character 7
A/R
A/R
Profile Name Character 8
A/R
A/R
Profile Name Character 9
A/R
A/R
Profile Name Character 10
A/R
A/R
Profile Name Character 11
A/R
A/R
Profile Name Character 12
A/R
A/R
Profile Name Character 13
A/R
A/R
Profile Name Character 14
A/R
A/R
Profile Name Character 15
A/R
A/R
Profile Name Character 16
A/R
A/R
Profile Start Signal High Byte
0
0
0 = No delay, 1 = After delay, 2 = At Time/
day
Profile Start Signal Low Byte
A/R
A/R
Profile Start Time (Byte 4 - High)
A/R (Floating point
number)
The time, in elapsed seconds, from the
start trigger before a profile will begin if
Start Signal =1 (After Delay) or seconds
from midnight if Start Signal =2 (Time of
Day) Is zero if Start Signal =0 (No Delay)
Profile Start Time (Byte 3)
Profile Start Time (Byte 2)
Profile Start Time (Byte 1 - Low)
Profile Start Day High Byte
0
0
1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday,
7 = Sunday, 8 = Monday to Friday, 9 =
Monday to Saturday, 10 = Saturday And
Sunday, 11= All Week
Profile Start Day Low Byte
A/R
A/R
Profile Starting Setpoint High
0
0
0 = Current Setpoint, 1 = Current Process
Value
Profile Starting Setpoint Low
A/R
A/R
Profile Recovery High Byte
0
0
0 = Control to off, 1 = Restart profile, 2 =
Maintain last profile setpoint, 3 = Use con-
troller setpoint, 4 = Continue profile from
where it was when power failed
Profile Recovery Low Byte
A/R
A/R
Profile Recovery Time (Byte 4 - High)
A/R (Floating point
number)
The Profile Recovery Time (before the
recovery action will be used after power/
signal returns) in elapsed seconds. Is zero
if no recorder (RTC) fitted - function not
possible
Profile Recovery Time (Byte 3)
Profile Recovery Time (Byte 2)
Profile Recovery Time (Byte 1 - Low)
Profile Abort action High Byte
0
0
0 = Control to off, 1 = Maintain last profile
setpoint, 2 = Use controller setpoint
Profile Abort action Low Byte
A/R
A/R
Profile Cycles High Byte
A/R
A/R
1 to 9999 or 10,000 for “Infinite”
Profile Cycles Low Byte
A/R
A/R
Profile Number of Loops High Byte
0
0
The number of loops controlled by the
profile: 1 or 2
Profile Number of Loops Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R