Auto Hold on Ramps
Held if Auto-Hold set to Above Setpoint or Band
Held if Auto-Hold set to Below Setpoint or Band
Ramp Setpoint
(with Auto-Hold)
Hold Band
Process Variable
Ramp Setpoint
(without Auto-Hold)
Figure 53. Auto-Hold On A Ramp Segment
During a Ramp segment, the ramp is held at the cur-
rent setpoint value while the process is outside of the
hold band in the selected direction(s). The time taken
to complete the ramp is increased by the time taken by
the Auto-Hold.
Profile Cycles & Repeat Sequences
A profile can be configured to run itself from 1 to 9999
times or continuously using the Profile Cycles setting.
A profile ending with
Repeat then End will run the en-
tire sequence of profiles again from 1 to 9999 times
before ending.
PROFILE 4
PROFILE 31
PROFILE 7
Join (Profile 4 to Profile 31)
Join (Profile 31 to Profile 7)
Example: Runs profile 4 once, profile 31 three times & profile 7 once.
This sequence is repeated ten times.
Profile 31
Cycles = 3
Repeat Sequence = 10
Repeat Then End
(times to repeat = 10)
Profile 4
Cycles = 1
Profile 7
Cycles = 1
Figure 54. Profile Cycles & Repeats