140
Self-Tune Secondary Status
Value
Loop 2 Self-Tune Secondary Status
Dec
4442
20826
41652
RO
0
No Additional Information
Hex
115A
515A
A2B4
2
Manual Control Enabled (Self-Tune cannot run)
3
Control has On/Off element (Self-Tune cannot run)
4
Input not valid (Self-Tune cannot run)
5
Control Disabled (Self-Tune cannot run)
Loop 2 Anti Wind-Up Limit
Loop 2 Anti Wind-up Limit
Dec
4491
20875
41750
RW
Power level where integral action is suspended.
Adjustable from 10.0 to 100.0% of PID power.
Hex
118B
518B
A316
Loop 2 Motor Travel Time
Loop 2 Motor Travel Time
Dec
4443
20827
41654
RW
The motor travel time (from fully open to fully closed) for 3-point
stepping VMD control. Adjustable from 5 to 300 seconds.
Hex
115B
515B
A2B6
Loop 2 Minimum Motor on Time
Loop 2 Minimum Motor on Time
Dec
4444
20828
41656
RW
Minimum drive effort to begin moving valve for 3-point stepping
VMD control. In seconds, from 0.02 to 1/10 of Motor Travel Time
Hex
115C
515C
A2B8
Loop 2 Valve Break Action
Value
Loop 2 Sensor Break Action For VMD Control
Dec
4501
20885
41770
RW
0
Close Valve Output On
Hex
1195
5195
A32A
1
Open Valve Output On
Loop 2 Minimum Valve Position
Loop 2 Minimum Valve Postition
Dec
4476
20860
41720
RW
Minimum position to drive valve in VMD Mode
from the valve close limit+1% to 100.0%
Hex
117C
517C
A2F8
Loop 2 Maximum Valve Position
Loop 2 Maximum Valve Postition
Dec
4477
20861
41722
RW
Maximum position to drive valve in VMD Mode.
From 0.0% to the valve open limit-1%
Hex
117D
517D
A2FA
Loop 2 PID Set Select
Value
Loop 2 PID Set Selection
Dec
4467
20851
41702
RW
0
PID Set 1
Hex
1173
5173
A2E6
1
Gain Schedule Selected by SP
2
Gain Schedule Selected by PV
3
PID Set 2
4
PID Set 3
5
PID Set 4
6
PID Set 5
PID Set 2 - Primary Prop Band
PID Set 2 Primary Proportional Band For Loop 2
Dec
4447
20831
41662
RW
Primary Proportional Band for Gain Set 2. 1 display unit to 9999
units, but limited to 10 x scaled input span. 0 = On-Off control
Hex
115F
515F
A2BE
PID Set 2 - Secondary Prop Band
PID Set 2 Secondary Proportional Band For Loop 2
Dec
4448
20832
41664
RW
Primary Secondary Band for Gain Set 2. 1 display unit to 9999
units, but limited to 10 x scaled input span. 0 = On-Off control
Hex
1160
5160
A2C0
PID Set 2 - Integral Time
PID Set 2 Integral Time For Loop 2
Dec
4449
20833
41666
RW
Secondary Proportional Band for Gain Set 2.
1 display unit to 9999 units, but limited to 10 x scaled input span.
0 = On-Off control
Hex
1161
5161
A2C2