89
Input 1 Filter Time Constant
Input 1 Process Input Filter Time
Dec
1030
17414
34828
RW
Valid between 0.0 and 512.0
Hex
0406
4406
880C
Input 1 Process Variable
Process Input 1 Value
Dec
1031
17415
34830
RO
The current input 1 process value
Hex
0407
4407
880E
Input 1 Signal /Sensor Break Flag
Value
Process Input Break Status
Dec
1032
17416
34832
RO
0
1
Inactive
Active (break detected)
Hex
0408
4408
8810
Input 1 Signal Under Range Flag
Value
Process Input Under Range Status
Dec
1033
17417
34834
RO
0
1
Inactive
Active (under-range detected)
Hex
0409
4409
8812
Input 1 Signal Over Range Flag
Value
Process Input Over Range Status
Dec
1034
17418
34836
RO
0
1
Inactive
Active (over-range detected)
Hex
040A
440A
8814
Input 1 Cold Junction Compensation
Value
CJC Status
Dec
1035
17419
34838
RW
0
1
Disabled
Enabled (default)
Hex
040B
440B
8816
Input 1 Multi-Point Scaling Enable
Value
Multi-Point Scaling Status
Dec
1053
17437
34874
RW
0
1
Disabled
Enabled (valid only if the input type is linear)
Hex
041D
441D
883A
Input 1 Scale Point 1
Multi-Point Scaling Point 1
Dec
1054
17438
34876
RW
Percentage of the scaled input where multi-point scaling value 1
is applied. 0.1 to 100.0% *set to 100% ends scaling sequence
at that point.
Hex
041E
441E
883C
Input 1 Display Point 1
Multi-Point Scaling Display Value For Point 1
Dec
1055
17439
34878
RW
Value to display at multi-point scaling point. 1 Valid between the
scaled input lower & upper limits.
Hex
041F
441F
883E
Input 1 Scale Point 2
Multi-Point Scaling Point 2
Dec
1056
17440
34880
RW
Percentage of the scaled input where multi-point scaling value 2
is applied. 0.1 to 100.0% *set to 100% ends scaling sequence
at that point
Hex
0420
4420
8840
Input 1 Display Point 2
Multi-Point Scaling Display Value For Point 2
Dec
1057
17441
34882
RW
Value to display at multi-point scaling point 2. Valid between the
scaled input lower & upper limits.
Hex
0421
4421
8842
Input 1 Scale Point 3
Multi-Point Scaling Point 3
Dec
1058
17442
34884
RW
Percentage of the scaled input where multi-point scaling value 3
is applied. 0.1 to 100.0% *set to 100% ends scaling sequence
at that point
Hex
0422
4422
8844
Input 1 Display Point 3
Multi-Point Scaling Display Value For Point 3
Dec
1059
17443
34886
RW
Value to display at multi-point scaling point 3. Valid between the
scaled input lower & upper limits.
Hex
0423
4423
8846