150
Alarm 6 Inhibit Enable/Disable
Value
Alarm 6 Power-up/Setpoint Change Inhibit
Dec
6227
22611
45222
RW
0
Disabled
Hex
1853
5853
B0A6
1
Enabled
Alarm 6 Status
Value
Alarm 6 Status
Dec
6228
22612
45224
RO
0
Inactive
Hex
1854
5854
B0A8
1
Active
Alarm 6 Inhibit Status
Value
Alarm 6 Inhibit Status
Dec
6229
22613
45226
RO
0
Not Inhibited
Hex
1855
5855
B0AA
1
Inhibited
Alarm 6 Label
Main Language Name For Alarm 6 In Status Screen
Dec
6231
22615
45230
RW
8 ASCII characters replacing the title “Alarm 6” in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1857
5857
B0AE
Alarm 6 Alternate Label
Alternate Language Name For Alarm 6 In Status Screen
Dec
6232
22616
45232
RW
8 ASCII characters replacing the title “Alarm 6” in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1858
5858
B0B0
Alarm 6 Minimum Duration
Alarm 6 Minimum Duration
Dec
6233
22617
45234
RW
Minimum time alarm 6 must be passed its threshold before activating
(deactivation is not affected by this parameter). From 0 to 9999 secs
Hex
1859
5859
B0B2
Alarm 7 Input Source
Value
Source
Dec
6239
22623
45246
RW
0
Input 1
Hex
185F
585F
B0BE
1
Input 2
2
Aux A Input
3
Control Loop 1 Primary Power
4
Control Loop 1 Secondary Power
5
Control Loop 2 Primary Power
6
Control Loop 2 Secondary Power
7
Loop 1
8
Loop 2
Alarm 7 Type
Value
Alarm 7 Type
Dec
6240
22624
45248
RW
0
Unused
Hex
1860
5860
B0C0
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Input Rate of Change
6
Input/Sensor Break Alarm
7
Loop Alarm
10
% memory used
11
High Power Alarm
12
Low Power Alarm