![GS Chromalox 4081 Скачать руководство пользователя страница 147](http://html1.mh-extra.com/html/gs/chromalox-4081/chromalox-4081_installation-and-operation-manual_2274774147.webp)
139
Loop 2 Self-Tune Engage/Disengage
Value
Self-Tune Engage/Disengage For Loop 2
Dec
4426
20810
41620
RW
0
Self-Tune OFF
Hex
114A
514A
A294
1
Self-Tune ON
Loop 2 Loop Alarm Type
Value
Loop Alarm Type For Loop 2
Dec
4427
20811
41622
RW
1
User Defined Time
Hex
114B
514B
A296
2
Automatic (2x Integral Time)
Loop Alarm Time
Loop Alarm Activation Time
Dec
4428
20812
41624
RW
1 to 5999 Seconds after output loop 2 power reaches saturation
Hex
114C
514C
A298
Loop 2 Primary Power
Loop 2 Primary Power Level
Dec
4429
20813
41626
RO
The current loop 2 primary power level (0 to 100%)
Hex
114D
514D
A29A
Loop 2 Secondary Power
Loop 2 Secondary Power Level
Dec
4430
20814
41628
RO
The current loop 2 secondary power level (0 to 100%)
Hex
114E
514E
A29C
Loop 2 Combined Power
Loop 2 Combined Primary & Secondary Power Level
Dec
4431
20815
41630
RO
The current loop 2 combined PID power level (-100 to 100%)
Hex
114F
514F
A29E
Loop 2 Pre-Tune Status
Value
Pre-Tune Status For Loop 2
Dec
4432
20816
41632
RO
0
Inactive
Hex
1150
5150
A2A0
1
Active
Loop 2 Self-Tune Status
Value
Self-Tune Status For Loop 2
Dec
4433
20817
41634
RO
0
Inactive
Hex
1151
5151
A2A2
1
Active
Loop 2 Loop Alarm Status
Value
Loop Alarm Status For Loop 2
Dec
4434
20818
41636
RO
0
Inactive
Hex
1152
5152
A2A4
1
Active
Loop 2 Input Failure Pre-set Power
Loop 2 Input Sensor Break Pre-Set Power
Dec
4435
20819
41638
RW
The pre-defined power output applied if input signal is lost
0 to 100% (-100% to 100% for dual control).
Hex
1153
5153
A2A6
Loop 2 Auto Pre-Tune
Auto Pre-Tune at Every Power-up For Loop 2
Dec
4436
20820
41640
RW
0
Inactive
Hex
1154
5154
A2A8
1
Active
Pre-Tune Secondary Status
Value
Loop 2 Pre-Tune Secondary Status
Dec
4441
20825
41650
RO
0
No Additional Information
Hex
1159
5159
A2B2
1
PV within 5% (Pre-Tune cannot run)
2
Manual Control Enabled (Pre-Tune cannot run)
3
Control has On/Off element (Pre-Tune cannot run)
4
Input not valid (Pre-Tune cannot run)
5
Control Disabled (Pre-Tune cannot run)
6
Profile Running (Pre-Tune cannot run)
7
Setpoint Ramping (Pre-Tune cannot run)
Содержание Chromalox 4081
Страница 2: ...B ...