92
User Calibration Type
Value
Calibration Type
Dec
1085
17469
34938
RW
0
1
2
None (input 1 base calibration used)
Single Point Calibration
Two Point Calibration
Hex
043D
443D
887A
User Calibration Point - Low Value
Two Point Calibration Low Point
Dec
1086
17470
34940
RW
The input value at which the Low Offset will be applied. Valid
between input 1 scaled input lower & upper limits.
Hex
043E
443E
887C
User Calibration Point - Low Offset
Two Point Calibration Low Offset Value
Dec
1087
17471
34942
RW
The Low Offset value applied to the reading at the Low Calibra-
tion Point 0.0 to 100.0%.
Hex
043F
443F
887E
User Calibration Point - High Value
Two Point Calibration High Point
Dec
1088
17472
34944
RW
The input value at which the High Offset will be applied Valid
between input 1 scaled input lower & upper limits.
Hex
0440
4440
8880
User Calibration Point - High Offset
Two Point Calibration High Offset Value
Dec
1089
17473
34946
RW
The High Offset value applied to the reading at the High Calibra-
tion Point 0.0 to 100.0%.
Hex
0441
4441
8882
Universal Process Input 2 Parameters
Parameter Name & Register Address
Integer Int +1
Float
Access Values & Description
Universal Input 2 Usage
Value
Process Input Type
Dec
1166
17550
35100
RW
0
Standard
Hex
048E
448E
891C
1
Feedback signal for Input 1
2
Redundant Sensor
(backup for Input 1 Thermocouple or RTD)
3
Not Used (or Indication only)
Universal Process Input 2 Type
Value
Process Input Type
Dec
1100
17484
34968
RW
0
B Type Thermocouple
Hex
044C
444C
8898
2
C Type Thermocouple
4
D Type Thermocouple
6
E Type Thermocouple
8
J Type Thermocouple
10
K Type Thermocouple
12
L Type Thermocouple
14
N Type Thermocouple
16
R Type Thermocouple
18
S Type Thermocouple
20
T Type Thermocouple
22
PtRh 20%: 40% Thermocouple
24
PT100 RTD
26
NI120 RTD
28
0 to 20mA DC
29
4 to 20mA DC