176
Returns the number of unused segments remaining in the instrument. The number will be between 0 and 255,
depending on how many have been used in the profiles so far created.
The instrument replies to each profile or segment creation, edit or delete message with an Edit Response Message.
The same format is used when replying to the Get Segments Remaining request.
Get Segments Remaining - Request (to instrument)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The network address ID of the instrument.
Function Code
23
17
Requires the multi read/write function.
Read Start Address High Byte
32
20
Read Start Address Low Byte
6
6
Read Quantity Of Registers High
0
0
Read Quantity Of Registers Low
1
1
Write Start Address High
32
20
Write Start Address Low
6
6
Write Quantity Of Registers High
0
0
Write Quantity Of Registers Low
1
1
Byte Count
2
2
Command Code High Byte
83
53
Command Code Low Byte
82
52
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.
Edit Response Message - Response (to instrument)
Field Name
Data
Comments
Dec
Hex
Unit Address
A/R
A/R
The network address ID of the instrument
Function Code
23
17
The multi read/write function
Byte Count
2
2
Command Code High Byte
A/R
A/R
Two data bytes containing the
Command Response data (see below)
Command Code Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.
Get Segments Remaining
Edit Response Message from Instrument
Содержание Chromalox 4081