145
Alarm 2 Rate of Change Value
Process Variable Rate of Change Alarm Threshold
Dec
6166
22550
45100
RW
Value for Rate of Change Alarm. Alarm 2 activates when PV
change exceeds this level. From 0.0 to 99999
Hex
1816
5816
B02C
Alarm 2 Hysteresis
Alarm 2 Hysteresis Value
Dec
6162
22546
45092
RW
Deadband value (on “safe” side of alarm), through which signal must
pass before Alarm 2 deactivates. Limited by the input scaling span
Hex
1812
5812
B024
Alarm 2 Inhibit Enable/Disable
Value
Alarm 2 Power-up/Setpoint Change Inhibit
Dec
6163
22547
45094
RW
0
Disabled
Hex
1813
5813
B026
1
Enabled
Alarm 2 Status
Value
Alarm 2 Status
Dec
6164
22548
45096
RO
0
Inactive
Hex
1814
5814
B028
1
Active
Alarm 2 Inhibit Status
Value
Alarm 2 Inhibit Status
Dec
6165
22549
45098
RO
0
Not Inhibited
Hex
1815
5815
B02A
1
Inhibited
Alarm 2 Label
Main Language Name For Alarm 2 In Status Screen
Dec
6167
22551
45102
RW
8 ASCII characters replacing the title “Alarm 2” in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1817
5817
B02E
Alarm 2 Alternate Label
Alternate Language Name For Alarm 2 In Status Screen
Dec
6168
22552
45104
RW
8 ASCII characters replacing the title “Alarm 2” in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1818
5818
B010
Alarm 2 Minimum Duration
Alarm 2 Minimum Duration
Dec
6169
22553
45106
RW
Minimum time alarm 2 must be passed its threshold before activating
(deactivation is not affected by this parameter). From 0 to 9999 secs
Hex
1819
5819
B032
Alarm 3 Input Source
Value
Source
Dec
6175
22559
45118
RW
0
Input 1
Hex
181F
581F
B03E
1
Input 2
2
Aux A Input
3
Control Loop 1 Primary Power
4
Control Loop 1 Secondary Power
5
Control Loop 2 Primary Power
6
Control Loop 2 Secondary Power
7
Loop 1
8
Loop 2
Alarm 3 Type
Value
Alarm 3 Type
Dec
6176
22560
45120
RW
0
Unused
Hex
1820
5820
B040
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Input Rate of Change