Alarm 5 Label
Main Language Name For Alarm 5 In Status Screen
Dec
6215
22599
45198
RW
8 ASCII characters replacing the title “Alarm 5” in alarm status
screens when main display language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1847
5847
B08E
Alarm 5 Alternate Label
Alternate Language Name For Alarm 5 In Status Screen
Dec
6216
22600
45200
RW
8 ASCII characters replacing the title “Alarm 5” in alarm status
screens when the alternate language is used, read/written with
Modbus functions 16 or 23. Valid characters are
0 to 9, a to z, A
to Z, plus ß ö ( ) - and _.
Hex
1848
5848
B090
Alarm 5 Minimum Duration
Alarm 5 Minimum Duration
Dec
6201
22585
45170
RW
Minimum time alarm 5 must be passed its threshold before activating
(deactivation is not affected by this parameter). From 0 to 9999 secs
Hex
1839
5839
B072
Alarm 6 Input Source
Value
Source
Dec
6223
22607
45214
RW
0
Input 1
Hex
184F
584F
B09E
1
Input 2
2
Aux A Input
3
Control Loop 1 Primary Power
4
Control Loop 1 Secondary Power
5
Control Loop 2 Primary Power
6
Control Loop 2 Secondary Power
7
Loop 1
8
Loop 2
Alarm 6 Type
Value
Alarm 6 Type
Dec
6224
22608
45216
RW
0
Unused
Hex
1850
5850
B0A0
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Input Rate of Change
6
Input/Sensor Break Alarm
7
Loop Alarm
10
% memory used
11
High Power Alarm
12
Low Power Alarm
Alarm 6 Value
Value at which Alarm 6 Activates
Dec
6225
22609
45218
RW
Limited by input scaling for alarm types 1 to 4
Not used for alarms 5, 6 or 7. 0 to 100% for alarms 10 to 12.
Hex
1851
5851
B0A2
Alarm 6 Rate of Change Value
Process Variable Rate of Change Alarm Threshold
Dec
6230
22614
45228
RW
Value for Rate of Change Alarm. Alarm 6 activates when PV
change exceeds this level. From 0.0 to 99999
Hex
1856
5856
B0AC
Alarm 6 Hysteresis
Alarm 6 Hysteresis Value
Dec
6226
22610
45220
RW
Deadband value (on “safe” side of alarm), through which signal must
pass before Alarm 6 deactivates. Limited by the input scaling span
Hex
1852
5852
B0A4