115
Digital Output 1 Function
Value
Digital Output 1 Function
Dec
10100
26484
52968
RW
0
Disabled
Hex
2774
6774
CEE8
1
Loop 1 Primary Output Power
2
Loop 1 Secondary Output Power
3
Loop 1 VMD Open
4
Loop 1 VMD Close
5
Loop 2 Primary Output Power
6
Loop 2 Secondary Output Power
7
Loop 2 VMD Open
8
Loop 2 VMD Close
9
OR Alarm Event Direct
10
OR Alarm Event Reverse
11
AND Alarm Event Direct
12
AND Alarm Event Reverse
Output 1 OR Alarm Selection
Value
If Bit = 1, Alarm n is Included in OR Selection
Dec
10107
26491
52982
RW
2
Alarm 1
Hex
277B
677B
CEF6
3
Alarm 2
4
Alarm 3
5
Alarm 4
6
Alarm 5
7
Alarm 6
8
Alarm 7
Output 1 OR Event Selection
Value
If Bit = 1, Event n is Included in OR Selection
Dec
10108
26492
52984
RW
2
Event 1
Hex
277C
677C
CEF8
3
Event 2
4
Event 3
5
Event 4
6
Event 5
7
Profile Running
8
Profile End
Output 1 AND Alarm Selection
Value
If Bit = 1, Alarm n is Included in AND Selection
Dec
10109
26493
52986
RW
2
Alarm 1
Hex
277D
677D
CEFA
3
Alarm 2
4
Alarm 3
5
Alarm 4
6
Alarm 5
7
Alarm 6
8
Alarm 7