English (GB)
23
Fig. 26
Mounting of controller to the wall
8.3 Electrical connection
The operating voltage and frequency are marked on the controller
nameplate. Make sure that the controller is suitable for the
electricity supply on which it will be used.
All cables/wires must be fitted through the cable entries and
gaskets (IP56).
The power supply socket must be placed near the cabinet as the
controller is supplied with a 1.5 m cable, a Schuko plug for
single-phase and a CEE plug for three-phase pumps.
Maximum back-up fuse is stated on the controller nameplate.
If required according to local regulations, install an external mains
switch.
8.4 Setting of LC 221
Only the start level corresponding to the inlet level to the
collecting tank needs to be set. All other values are preset but
can be adjusted if required.
Select the height of the inlet pipe, 180, 250 or 315 mm above
floor level, using the buttons
and
, and press the button
to save the desired value. If the height of the inlet pipe is between
two values, e.g. 220 mm above the floor, choose the nearest
lower value (180 mm). Now the controller is ready for automatic
mode.
The following values can be changed, if necessary:
Start level
The start level must be set according to the inlet pipe height
above floor level (180, 250 and 315 mm). Stop and alarm levels
are preset.
Rated current
Preset value from factory according to the rated current of the
motor. The protection against pump blockage is a preset value for
overcurrent.
Stop delay
The stop delay increases the effective volume and reduces the
quantity of residual water in the tank. It also prevents water
hammer. The non-return valve closes more softly. The preset
value is 0.
Start delay
Normally there is no need to make adjustments for lifting stations
except on a houseboat or pontoon boat. The preset value is 0.
Alarm delay
High temporary inflow can cause short-time high-level alarm.
This situation may arise when a backwash filter of a swimming
pool is connected to Multilift MD. Preset value is 5 seconds.
Maintenance interval
The maintenance/service interval can be set to 0, 3, 6 or
12 months and is indicated in the "SERVICE" display (no acoustic
signal).
Reset alarm
It is possible to set the controller to reset some alarms
automatically when the fault disappears; however, most alarms
must be reset manually. See section
. Preset value is AUTO.
Reset to factory settings
The controller will reboot, and start-up settings will have to be
made again. See section
8.4.1 External alarm
Lifting stations are often installed in sumps below the basement
of buildings. That is the deepest point in the building, and an
additional alarm level switch can be placed outside the lifting
station to detect flooding caused by leakages, pipe bursts or
groundwater inflow.
The external alarm can be connected to a level switch (230 V /
2 A) at terminals 13, 14.
TM
05
19
40
40
11
Warning
LC 221 must be connected in accordance with the
rules and standards in force for the application in
question.
Warning
Before opening the cabinet, switch off the mains
supply.
Содержание Multilift MD
Страница 2: ...2...
Страница 4: ...Table of contents 4 Multilift MD MLD UA 621 CN 647 JP 671 Appendix 699...
Страница 36: ...BG 36 5 2 1 LC 221 Multilift MD22 MLD22 5 2 LC 221...
Страница 39: ...BG 39 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2...
Страница 40: ...BG 40 1 1 1 2 2 2 6 4...
Страница 55: ...BG 55 3 a 10 4 b LED F011 F012 3 3 3 60 33 c TEMP F005 F006 LC 221 8 4 LC 221 ON OFF AUTO OFF S3 12 10 4 4 a 24...
Страница 184: ...Espa ol ES 184...
Страница 244: ...GR 244 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2 Alarm...
Страница 245: ...GR 245 1 1 1 2 2 2 6 4...
Страница 247: ...GR 247 6 3 OFF AUTO 13 13 TM05 1809 3811 EXIT EXIT R_03 A 3 9 007200 000020 20 01 20 20 F006 01 F002 R_02 R_01 F_01...
Страница 260: ...GR 260 3 a 10 4 b LED F011 F012 3 3 3 60 33 c F005 F006 LCD 221 8 4 LC 221 ON OFF AUTO OFF S3 12 10 4 4 a 24...
Страница 629: ...UA 629 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2 Setup...
Страница 630: ...UA 630 1 1 1 2 2 2 6 4...
Страница 632: ...UA 632 6 3 ON OFF AUTO 13 13 TM05 1809 3811 EXIT R_03 A 3 9 007200 000020 20 01 20 20 F006 01 F002 R_02 R_01 F_01...
Страница 645: ...UA 645 3 a 10 4 b F011 F012 3 3 3 60 33 c TEMP F005 F006 LC 221 8 4 LC 221 ON OFF AUTO OFF S3 12 10 4 4 a 24...
Страница 655: ...CN 655 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2...
Страница 656: ...CN 656 1 1 1 2 2 2 6 4...
Страница 658: ...CN 658 6 3 ON OFF AUTO 13 13 TM05 1809 3811 EXIT R_03 A 3 9 007200 000020 01 20 20 20 F006 01 F002 R_02 R_01 F_01...
Страница 660: ...CN 660 Man Auto ON OFF AUTO OFF ON OFF AUTO OFF 30 14 TM05 3455 0616...
Страница 680: ...JP 680 6 LC 221 6 1 LC 221 11 11 LC 221 TM05 1861 3811 1234 AUTO 6 3 6 2...
Страница 681: ...JP 681 2 1 1 1 2 2 2 6 4...
Страница 683: ...JP 683 6 3 ON OFF AUTO 13 13 TM05 1809 3811 EXIT EXIT R 03 A 3 9 007200 000020 20 01 20 20 F006 01 F002 R 02 R 01 F 01...
Страница 685: ...JP 685 LED Man Auto LED ON OFF AUTO OFF ON OFF AUTO OFF LED 30 14 TM05 3455 0412...
Страница 698: ...JP 698 13 1 2...
Страница 699: ...Appendix 699 Appendix 1 Fig A Dimensional sketches MD TM05 0441 1011...
Страница 700: ...Appendix 700 Fig B Dimensional sketches MLD TM05 0442 1011...
Страница 701: ...701...
Страница 702: ...702...