Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
30
4.4 Connections to other subsystems - system output
From
GENO-OSMO-X
control unit
to component
Line
Signal
Colour
System output Tank
68
Digital signals BB1 for regis-
tration of filling level of pure
water tank BB1CL1
LiYY 5x0.25 mm²
+24 V=
69
System OFF
BB1CL1
70
System ON / bypass closed
BB1CL2
71
Bypass closed / dry run pro-
tection of pressure booster
OFF
BB1CL3
72
Dry-run protection of pressure
booster ON
BB1CL4
Or alternatively
86
Analogue signals BB1 for
registration of filling level of
pure water tank BB1CL1
LiYY 3x0.34 mm²
+ 24 V=
WH
87
IN
BN
PE
Shield
YE-GN
24
RO1 V4 (first permeate)
or
RO1 V7 (blending valve)
H05VV-F 2x0.5 mm²
24 V=
BN
25
GND
BU
System output Online
84
Pressure measuring transducer
RO1 CP2 0…6 bar
LiYcY 2x0.25 mm²
+ 24 V=
WH
85
In
BN
PE
Shield
4.5 Connections to other subsystems – Residual hardness monitoring system NX1CQ1
for pre-treatment by water softener
From
GENO-OSMO-X
control unit
to component
Line
Signal
14
GENO-softwatch Komfort ter-
minals 16/17
LiYY 4x0.25 mm²
Com
15
N.O.
66
GENO-softwatch Komfort ter-
minals 8/10 and wire jumper be-
tween 7/12
+24 V=
67
DI9
4.5.1 Connections to other subsystems – Residual hardness monitoring system
NX1CQ1 for pre-treatment by water softener (GENO-Softwatch Komfort, from serial no.
40342)
From
GENO-OSMO-X
control unit
to component
Line
Signal
14
GENO-softwatch Komfort ter-
minals 18/19
LiYY 4x0.25 mm²
Com
15
N.O.
66
GENO-softwatch Komfort ter-
minals 10/12 and wire jumper
between 9/14
+24 V=
67
DI9
Содержание GENO-OSMO-X
Страница 2: ......