Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
48
4.2 Installer level (Code 113)
The installer level contains parameters that might have to be
adapted to the conditions on site during the start-up. Access to
the menu is protected by Code 113.
Note:
The parameters marked with (*) must not be modified in
the reverse osmosis system series GENO-OSMO-X!
Parameters
Factory
setting
Setting
range
Comment
Output logic
Release FU pump
RO1P1A1
NOC
NOC/
NCC
The GENO-OSMO-X control
unit has to establish a con-
nection between its voltage-
free contact terminals 12/13
and the frequency converter
terminals 1/2 for the pump to
work
Dosing Function
RO1P2 and
RO1P3 (*)
Pulse
Pulse/
N.C./N.O.
Only Pulse is admissible as
output signal to activate the
dosing pump(s)!
Function
Pulse outputs
regulating valves(*)
Step
Step/relay
Only Step is admissible as
output signal to activate the
regulating valves!
Function
RO1V5/V6/V8
RO1V6
RO1V5
RO1V6
RO1V8
Connection terminals 22/23
are switchable:
RO1V6
= bypass (opens if
level BB1CL3 is undershot,
closes if level
BB1CL2) is exceeded
RO1V5
= blending is always
open when the high-pressure
pump is running
RO1V8
= Membrane degas-
sing (actuated when system in
operation)
Содержание GENO-OSMO-X
Страница 2: ......