Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
46
4.1 User programming level
The user programming level can be accessed without entering a
Code.
Parameters
Factory
setting
Setting
range
Comment
Operating mode
Locked
Locked/
Flushing/
Manual operation/
Automatic
The desired operating mode
(except for Locked) has to be
started in the Info level by
means of the I/O button (the
colour of the button changes
from red to green):
Locked
= delivery state, no
system operation possible
Flushing
= flushing volume
stored in the system size will
be flushed to the drain once
Manual operation
(not possi-
ble in case of system output
Online) = permeate production
continues as long as the sys-
tem stays switched on via the
I/O button. No switch-off com-
mand via tank full detection will
be processed.
Automatic operation
= per-
meate is produced subject to
the level in the permeate tank
or the permeate pressure
Содержание GENO-OSMO-X
Страница 2: ......