Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
50
Parameters
Factory
setting
Setting
range
Comment
Output logic
Volt.-free contact
Error
NOC
NOC/
NCC
Switching behaviour of fault
signal contact terminals 7/9:
NCC
= contact opens in case
of Mains Off or in case a sig-
nal occurs
NOC
= contact closes if an er-
ror occurs
Output logic
Release NX1Q1
NOC
NOC/
NCC
Switching behaviour
Release NX1Q1 terminal
14/15:
NOC
= contact closes in case
of release.
NCC
= contact opens in case
of release.
Input logic
Minimum pressure
switch
RO1CP1(*)
NOC
NOC/
NCC
Switching behaviour of low
pressure switch terminals
54/55:
NOC
= contact is closed by
means of sufficient pressure
in the inlet
NCC
= contact is opened by
means of sufficient pressure
in the inlet
Input logic
Fault signal
RO1A1 (*)
NCC
NOC/
NCC
If the frequency converter
works properly, it has to es-
tablish a connection between
its voltage-free contact termi-
nals 10/11 and terminals
56/57 of the GENO-OSMO-X
control unit