Reverse osmosis system
GENO-OSMO-X
Order no. 134 750 927-inter Edited by: phar/mrie G:\BA-750927-inter_134_GENO-OSMO_X.docx
52
Parameters
Factory
setting
Setting
range
Comment
Input logic
Error
empty signal
RO1CL.2 (*)
NOC
NOC/
NCC
Contact type suction lance
dosing pump RO1 P2 termi-
nals 63/64 (empty signal)
resp. 63/65 (pre-warning):
NOC
= open contact means
level has been undershot
NCC
= closed contact means
level has been undershot
Input logic
Pre-warning
RO1CL1 (*)
NOC
NOC/
NCC
Input logic
Residual hardness
NX1CQ1(*)
NOC
NOC/
NCC
Contact type alarm + limit
value terminals 66/67 from
monitoring device for residual
hardness:
NOC
= Contact opens in case
of power failure, malfunction or
if the limit value is exceeded
NCC
= Contact is closed in
case of alarm or if the limit
value is exceeded.
Input logic
Level
BB1CL1 … CL4
CL1: NCC
CL2…4:
NOC
NOC/
NCC
The topmost level is declared
as NCC by the factory, so that
an error in the filling level
measurement can be detected.
NOC
= contact open means
level has been undershot
NCC
= contact closed means
level has been undershot
Input logic
Programmable fault
signal input
NOC
NOC/
NCC
Input logic terminals 60/61:
Input logic
Error
empty signal
RO1CL4 (*)
NOC
NOC/
NCC
Contact type suction lance
dosing pump RO1P3 termi-
nals 50/62 (empty signal)
resp. 50/51 (pre-warning):
NOC
= contact open means
level has been undershot
NCC
= contact closed means
level has been undershot
Input logic
Signal
pre-warning
RO1CL3(*)
NOC
NOC/
NCC
Input logic
Overpressure switch
RO1 CP3
NCC
NOC/
NCC
Contact type terminals 58/59:
NOC
= too high system pres-
sure closes contact
NCC
= too high system pres-
sure opens contact
Solenoid valve out-
puts
intermittend
intermittend/
constant
Applies to all valve outputs.
Intermittend
= valve output
with timed pulses.
Constant
= valve output with
constant pulses.