8-2-2 Call Points to Evacuate.
Enables or disables a system wide setting that a report of fire from a call-point automatically starts evacuation.
Evacuation means any Sounder Group settings will be ignored and all sounders will be operated
immediately.
8-3 Memory -
8-3-1 Clear Customer Flash Memory
BEWARE, ENGINEERS ONLY
Programming functions that are associated with management of the Panel memory.
This function erases all of the site specific data from the customer Flash memory on the SIM CARD. This is the
majority of the programmed settings.
DO NOT erase this data if you were supplied with pre-programmed site data.
It is not recommended that this function is carried out from a Repeater as the erase will take a few seconds and
during that time communication to the Repeater will be lost.
If the Customer Flash Memory is cleared:
All Sounder Groups will have continuous sounder operation
All Sounder Group definitions will be cleared
The Sounder Configuration will be set to PRESET
All Zone text will be cleared
All Zone Sounder and I/O group settings will be cleared
All Zone definitions will be cleared (no devices assigned)
Zone sounder delay settings will be cleared
The company name will be cleared
All device text will be cleared
All device specific settings will be cleared
All sensitivity settings will be reset
All delay settings will be cleared
The language will be reset to English
All I/O group definitions will be cleared
User access to all programming functions will be denied
NOTE: Disabled sounders will not be activated.
.
NOTE: The Installer Access Code will not be cleared. After clearing the Customer Flash Memory it
is essential to perform a system Master Reset to ensure the new settings are sent to all.
(Settings are otherwise only sent when they are changed using the programming functions).