4-3 Disable Sounders
Allows specific sounders to be disabled or Enabled.
Disabled sounders will not be operated regardless of Sounder Configuration, Sounder Groups and evacuate
requests.
‘E’
indicates enabled
‘D’
indicates disabled
When programming mode is exited all sounders that have been disabled can be reviewed using the
DISABLED (QUEUE REVIEW) button.
4-4 Assign Sounder Group to Device
Allows a Sounder Group to be assigned to a detector. When the detector goes into alarm then the assigned
Sounder Group will be activated (Sounder Groups only function when Sounder Configuration is set to
PROGRAMMED).
4-5 Inhibit Sounders for Device
Allows a device to be set so that is does not operate certain Sounder Groups. (Sounder Groups only function
when Sounder Configuration is set to PROGRAMMED).
The options are:
COMMON
The Common Sounder Group (512) is not activated when the device detects fire
ZONAL
The Zone Sounder Group for the device is not activated when the device detects fire
ALL
No sounders are activated when the device detects fire
Inhibiting all sounders for a device will inhibit all sounders even if the Sounder Configuration is set to PRESET.
COMMON or ZONAL inhibits will not inhibit the Sounder Group directly assigned to a device (function 4-4
Assign Sounder Group to Device) if that device detects fire.
NOTE:
When a fire occurs all the Sounder Group information for the detector in fire is combined:
the device Sounder Group is combined with the Zone Sounder Group and the Common
Sounder Group. ‘P’ pulsing will override ‘S’ silent and ‘C’ will override ‘P’ pulsing.
Do not use this function to assign sounders to Sounder Groups; it will have no effect.
Assign sounders to Sounder Groups using function 4-2 Configure Sounder Groups.