Unassigned Detector Tests
If the detectors have not been assigned to a Zone then they can only be tested in normal (Active) mode. Using the
programming menu ensure the system is set to Active Mode then exit programming mode and press SYSTEM
RESET.
Carry out a fire test on each detector. Confirm the LED lights on the detector under test. Confirm that the fire is
reported correctly at the Panel (and any Repeaters). Confirm that the sounders operate.
Note that sounders and detectors can be inhibited or delayed using the advanced features in the programming
menus. If the sounders do not operate as expected first verify all the settings for the sounders and the device
under test.
WRAPPING UP INSTALLATION AND COMMISSIONING
At this stage you may program the more advanced features of the system. The basic minimum usually involves
assigning text labels to the device and Zones.
Once you have completed this or if you have a pre-programmed SIM CARD then do not forget to carry out the
following steps:
Connect the batteries to the Panel as described in the Installation section of this manual.
Test that the battery monitoring is functional by temporarily removing the blue wire between the batteries.
After a few seconds the fault should be reported on the Panel.
When the blue wires are reconnected pressing SYSTEM RESET should clear the fault report.
Test that the primary supply monitoring is functional and that the battery system works. Switch off the AC
supply to each power supply unit in the Panel. After a few seconds the fault should be reported on the Panel.
Reconnect the AC supplies and press SYSTEM RESET.
Confirm that the system is in Active Mode - the SYSTEM ON LED is permanently lit.