CONTROLS
DISABLEMENTS
BUZZER SILENCE
The occurrence of any new fire or fault condition will initiate the operation of the internal buzzer. By pressing this
switch, the operation of the buzzer will be stopped until a new fire or fault appears on the system.
SYSTEM RESET
Soft resets the entire system. A soft reset should be satisfactory under almost all circumstances however a Master
Reset can be performed by cycling the power on the Panel (removing both primary AC and secondary DC supplies).
LAMP TEST
- General User Access (no code entry required)
Lights all the LEDS, turns on the LCD back light and sets all display pixels to black.
Lamp test only operates whilst the key is depressed.
SOUNDERS ACTIVATE / SILENCE
Activates all sounders. A second press de-activates all sounders.
The adjacent LED is illuminated whilst the sounders are activated.
It is possible to define if pressing the SOUND ALARMS button will activate the systems Fire I/O's.
AUXILIARY RELAYS
When this button is activated all relays and I/O modules connected to the system have their outputs disabled. This
includes the normally energised FAULT relay, the FAULT I/O group and all ALARM I/O groups. When these outputs are
disabled the button LED is illuminated. Pressing the button again restores normal relay and I/O module operation.
SOUNDERS DISABLE
When this button is activated, all sounders will be disabled and the LED will be lit. Pressing it again will reenable the
sounders and the LED will turn off.
SELECTED DETECTORS
Via the programming menus individual sensors may have selective disablement turned on. When this button is
activated those sensors that have selective disablement turned on will not generate a fire alarm condition. When
activated the adjacent LED is illuminated.
If no devices have selective disablement turned on, then pressing this button will have no effect.
Pressing the button again restores normal sensor operation.
DELAYS ACTIVE
Only when this button is activated (and the adjacent LED illuminated) will the sounder and I/O module delays
operate. Pressing the button again will deactivate the delays and will result in immediate sounder and I/O operation.
Under any fire condition the delays will be activated. If during the course of these delays this button is pressed the
delays will be overridden and the sounders and together with any other fire indicating equipment, will be activated.
NOTE: If an alarm has been detected it is necessary to silence the alarms using SOUNDER SILENCE
before the SYSTEM RESET button will operate.
NOTE:
F I/O'S ARE TO BE ACTIVATED BY EVAC. CONDITION, THIS WILL OVERRIDE THE DISABLEMENT.