Use 2 units of M3x5 mm
screws provided to fix Junior
Expansion Loop.
2 Male 8-way headers on
expansion board should fit
into the corresponding
female headers situated at
the back of the panel’s main
board.
Junior Expansion Loop Card
After fitting is completed
.
FITTING JUNIOR EXPANSION LOOP CARD
1 -
This operation should only be performed by qualified personnel.
2 -
Power to the panel should be completely removed, both primary and secondary (batteries)
supplies, before the installation process of the card is initiated.
3 -
After process is completed re-apply power to the panel.
4 -
Panel should be in installation mode. Green (Status) LED should be flashing.See function 8.4.1
5 -
Confirm using function 7.1 that devices attached to the 2nd loop are being detected by the panel.
6 -
No programming is required in order to enable the expansion loop card. The 2nd loop is automatically detected
by the panel.
Junior Expansion Loop Card
sits HERE
M
System power input
24V battery connection
N
N
M
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL