QUEUE REVIEW
FIRE
- General User Access (no code entry required)
If more than one fire has been detected then the LED next to this button will flash. Press the button to step
through all detected fires. Once all fires have been reviewed the LED will be constantly illuminated. Subsequent
fires will be added to the end of the queue and the LED will start to flash again.
After each button press the information will be displayed for 20 seconds. After that time the screen will revert
back to the first fire.
FAULT
- General User Access (no code entry required)
If more than one fault has been detected, or if a fault and fire have been detected, then the LED next to this
button will flash. Press the button to step through all reported faults. Once all faults have been reviewed the LED
will be constantly illuminated. Subsequent faults will be added to the end of the queue and the LED will start to
flash again.
After each button press the information will be displayed for 20 seconds. After that the screen will revert back to
the first fault (or fire).
TEST
- General User Access (no code entry required)
If the LED next to this button is illuminated then a test mode has been selected via the programming menus.
Pressing the button will show which sounders and zones have been set to test mode. If there are more zones
under test than can be displayed then pressing the button again will show the next set of zones under test.
The information is displayed for 15 seconds before the default display is restored.
DISABLED -
General User Access (no code entry required)
If the LED next to this button is illuminated then there is at least one disablement active in the system. Pressing
the button will display the disablements. If there are more disablements that can be displayed then pressing the
button again will show the next set of disablements and so on.
The information is displayed for 15 seconds before the default display is restored.
Possible disablements include - auxiliary relays, loops, zones, detectors and sounders.
NOTE: A SYSTEM RESET will clear all test modes.
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL