6-1-8 Global Sensitivity Set-up
6-1-9 Configure Timed Sensitivity
This function selects the sensitivity of all the detectors that have been set to GLOBAL SENSITIVITY.
Different settings can be entered for weekdays and for Saturday and Sunday.
Settings are :
HIGH
(alarm threshold of 45)
NORMAL
(alarm threshold of 55)
LOW
(alarm threshold of 65)
TIMED
If TIMED is selected then the night and day sensitivity settings used are based on whether it is night or day.
Set the night and day sensitivities using programming function 6-1-9. Define the time day and night start
using programming function 8-1-2.
The Pre-alarm levels are always 10 below the alarm thresholds.
Ensure that the system clock day, date and time are set correctly (function 8-1-1).
Note that in order to keep day/night and day settings consistent a day setting starts at sunrise (which is set by
function 8-1-2). This means that, for example, the Saturday setting will start at 8:00 AM on Saturday.
Allows the sensitivity to be set for day and night.
Settings are :
HIGH
(alarm threshold of 45)
NORMAL
(alarm threshold of 55)
LOW
(alarm threshold of 65)
NOTE: Smoke detectors set to LOW sensitivity do not meet the requirements of EN54 part 5.
NOTE:
Only detectors that have their sensitivity set to GLOBAL SENSITIVITY will have their
sensitivity changed, and then only if 6-1-8 Global Sensitivity Set-up has the day set to TIMED.
Smoke detectors set to LOW sensitivity do not meet the requirements of EN54 part 5.