LOOP 1
OUT
LOOP 1
RETURN
L2
L1
L2
L1
Device 1
Device 2
DEVICES
TCP/IP Connection
The use of a TCP/IP network may require the support and co-operation of the end users IT department. Be
sure that this support is available before deciding on this communications method.
Loop 1
Connector
Loop 2
Connector
NOTE: A maximum of 32 manual call-points can be fitted to the loop. If this value is exceeded the
response time for certain types of call-point will be excessive.
ANALOGUE LOOP(S)
The Analogue Loop provides the connection to all
the analogue addressable devices and loop
powered sounders. Unless the loop is completed
the panel will not be able to monitor its integrity
(open and short circuit monitoring).
Connection to the Analogue Loop for the Junior
panel as shown.
Devices that can be fitted to the Analogue Loop
include smoke sensors, heat sensors, Zone Monitor
Units (ZMU), I/O units, loop sounders and manual
call-points.
Wire the loop as shown.
Make the connections to the devices as specified on
the device data sheet. If no data sheet is available
make the connections as below:
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL