In order to initiate the programming procedure of the SAM’s the Panel has to be in INSTALLATION
MODE. See function 8.4.1.
The enabling of this mode is done on a per loop basis. When the loop is in ASET MODE the TEST LED
on the Panel, will be illuminated.
DO NOT remove or replace SAM’s while loop is powered. If one of these modules has to be replaced or
removed, first disconnect all supply sources to the panel.
Start SAM programming
Activate a blank SAM by either testing the device associated with it, either using the standard test procedure
for the device or by short-circuiting both SAM device wires (i.e. BLACK & RED) simulating in this case a device
activation. Smoke and heat detectors will have their alarm led permanently lit when activated. Sounders can
be set to activate for approximately 1 second, using function 7.3, every time a new SAM is activated (i.e. fire
condition). Upon activation of the conventional device and after a short delay (aprox. 3 seconds), the
associated SAM is programmed with the next available address. During this delay the panel will execute a
verification, where the new address and device will be confirmed and validated.
The programming of a new address can be monitored in four different ways, namely:
a)
Using function 7.1
, after a new SAM has been programmed the device count will increase by one and by
selecting the newly programmed address, the device type, address and analogue value can also be
confirmed.
b)
Using function 7.3
, the user can select to activate the sounders when a device enters the alarm state.
When in ASET mode, the sounders will be activated for approximately one second, each time a device
enters the fire condition and a new SAM address has been programmed. This will only affect loops where
the ASET MODE was enabled after entering the SOUNDERS ON TEST ACTIVATION mode.
c)
Using function 1.1
, the log of events can be used to verify the devices that have been programmed.
6-4-1 Activate ASET Mode (SAM)
CAUTION
A loop while in ASET mode will not offer any kind of protection
against fire conditions.
CAUTION
Removal of a SAM while loop is powered can corrupt programming of this
module and all other SAM’s present in the loop.
NOTE: A programmed SAM that has been RESET and re-enters the fire condition will force the
panel to activate the sounders without a new address being programmed. The panel will
activate the bells/sounders every time there is a new fire condition, regardless of it being
caused by a new address being attributed or not. Each new SAM programming should be
confirmed and monitored in order to avoid misleading information originating from SAM's
that have already been programmed.
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL