EN54 INFORMATION
In accordance with EN54 pt. 2 1997/AC:1999 clause 13.7, the maximum number of sensors and/or manual
call points in this panel, will not exceed 512 units.
The Fire Detection Control Panel complies with the requirements of EN54 pt. 2 and 4 1997/AC:1999. In
addition to the requirements of the above mentioned standard, the unit conforms to the following
optional functions:
OPTION
EN54 pt. 2 Clause
Indication
Fault Signals from Points
8.3
Controls
Delays for activation of outputs
7.11
Disablement of each Addressable point
9.5
Test Condition
10
Outputs
Outputs to fire alarm devices
7.8
In addition to the functions required by the standard EN54 pt. 2 1997/AC:1999, the panel supports ancillary
functions that are not required by the above mentioned standard, namely:
Ancillary Functions:
Panel network connection ports
Panel to PC programming software (upload / download) port.
Remote class change
Auxiliary relays outputs
Analogue Loops:
Each analogue loop can be connected to a maximum of 125 devices. According to EN54 pt. 2 clause 12.5.2,
in case of a short circuit or interruption of the analogue detection loop only a maximum of 32 detectors or
call points per loop, can be prevented at any one time, of transmitting a fire alarm. In order to assure
compliance with this clause, a loop isolator must be installed after every 32 detection devices.
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL