STATUS
FAULTS
CONTROLS
DISABLEMENTS
QUEUE REVIEW
KEYPAD
ZONES
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
SOUNDERS
ACTIVATE/ SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
DISABLED
TEST
FAULT
FIRE
MANUFACTURED IN THE E.U. TO THE
REQUIREMENTS OF EN54 Pt 2 & Pt 4 1999
INTRODUCTION
Commissioning involves checking that all connections have been made properly and that all hardware is
functioning correctly. This means the system must first be installed in accordance with the previous section of
this manual.
The panel is supplied set to ‘Installation mode’. In Installation Mode the green SYSTEM ON LED will flash on and
off. The panel will automatically detect and memorize all the devices connected to the loop in the system.
The default settings of the system mean that the unit will be ready to operate and detect a Fire incident from
the moment power is switched on. Therefore, the system will be fully functional without any additional
setting up. All further actions will tailor it to the requirements of the specific installation at hand.
Once the connections and hardware have been checked it is possible to get the basic fire alarm system up and
running very quickly - it is only necessary to have the system in Installation Mode for 90 seconds then set the
system to ‘Active Mode’. Programming of the system to provide more advanced functionality is covered in the
next section.
THE PANEL BUTTONS
COMMISSIONING
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL