REPEATER FIBRE-OPTIC
MINI-REP MB
The interface inside the Junior panel must have the link jumpers OFF.
The interface inside the Mini-Repeater must have the link jumpers ON.
PANEL =
REPEATER =
OFF
ON
LK1 & LK2
LINKS
Fibre-Optic External Connection
The dual fibre external fibre-optic connections should be made as follows:
J-NET-INT-FO
The repeater connections to the Fibre-Optic Interface are basically the same as for the Panel.
Panel
Repeater
NOTE: Make all connections with the power turned off to avoid risk of permanent damage to the
circuit boards.
Then continue to connect OUT of one
Repeater to IN of the next Repeater
following the same connection rules as
shown. When you reach the last Repeater in
the loop make the connections as follows:
Panel
Mini-Repeater
LOOP OUT
TX1
RX2
LOOP IN
RX1
TX2
Panel
Mini-Repeater
LOOP OUT
TX1
RX2
LOOP IN
RX1
TX2
Manufacturers of Fire Detection Equipment
globalfire.pt
INSTALLATION & COMMISSIONING MANUAL - V1. 03/2015
JUNIOR V4-L
- FIRE ALARM CONTROL PANEL