Symptoms
Cause
Action
Alert in the application
–
connection error
No connection with one or more
VERTEX control units
Check network connections between
the computer/ mobile device on which
the application is run
Alert in the application - 230V
on port
230 VAC mains voltage is
connected to one or more
device bus ports
Eliminate the mains voltage from the
port
Alert in the application
– too
many devices on the port
Too many devices are
connected to one or more
device bus ports
Reduce the number of devices to 64
Alert in the application
–
short-circuit on port
Short-circuit on one or more
device bus ports
Eliminate short-circuit
Alert in the application
–
DCASE communication error
Internal VERTEX error
Restart the device. If the problem
persists, contact the manufacturer.
Alert in the application
–
EEPROM error
EEPROM disconnected
Switch the device off.
Remove the top right-hand plug in the
device
Verify if EEPROM is connected
correctly
Switch the device on
EEPROM damage
Replace the memory or the device
Alert in the application
–
FLASH memory error
Damage of internal FLASH
memory in the device
Replace the device
Alert in the application
–
network not configured
The cluster of VERTEX control
units is not configured
– it has
to be configured even if it is
only one device
Use the VERTEX Firestarter to
configure the network
4. System start-
up
Red error message after
triggering an action
Action has not been triggered
on the VERTEX control unit(s)
No connection with one or more
VERTEX control units
Check network connections between
the computer/ mobile device on which
the application is run
57