EMERGENCY LIGHTING
Connect the emergency luminaires with back-up power supply according to one of the diagrams
below, according to the expected mode of operation (TA/TC).
In the TA non-continuous mode, connect the AC power supply to terminals
L*
and
N
of the emergency
module. In the TC continuous mode, additionally connect terminals
L*
and
L
. In the TC continuous
switchable mode, connect a switch to terminal L.
Connecting the emergency module in the TA mode (non-continuous)
CONNECTING THE NETWORK COMPONENTS
Connect the network components according to their own manuals.
SYSTEM CHECK
Before the start-up, verify the power supply wiring, structural cabling, DALI communication buses and
GSM connection according to the following steps.
POWER WIRING CHECK
Verify the presence of power on all devices in the lighting control system. Use the following hints:
•
VERTEX control units
o
POWER LED on the front panel is lit (solid)
•
ATLAS access point
o
POWER LED on the front panel is lit (solid)
Connecting the emergency module in the TC mode (continuous)
Connecting the emergency module in the TC mode (continuous switchable)
19