The value is stored as the Unix time (timestamp)
according to the set time zone.
2
4
UID
64
Luminaire ID No. corresponding to the sticker on the
luminaire. Stored as an integer (int 64) in the register.
Convert to hexstring to get a readable value:
Example:
Decimal integer:
240305920
value converted to hexstring:
E52C700
6
0,5
DaliPort
8
DALI port No. on which the device is located.
Values:
0
–
first port
1
–
second port
2
–
third port
6
0,5
TestGroup
8
Test group in which the device is located
Values:
255- no group
0-15
–
test group No.
7
1
DeviceType
8
Device type acc. to IEC62386-102.
Values:
0
:Fluorescent Lamp
1
:Emergency Lighting
2
:Discharge Lamps
3
:LowVoltage halogen lamps
6
: LED
8
0,5
ActualLevel
8
Current lighting brightness
Value range: 0 - 254
Values are in the
logarithmic scale. Use the following
formula to convert to percent:
8
0,5
PowerOnLevel
8
Brightness at lamp power-on.
Value range: 0 - 254
Values are in the logarithmic scale. Use the following
formula to convert to percent:
9
0,5
SystemFailureLevel
8
Brightness to be set in case of lamp failure.
Value range: 0 - 254.
255
–
do not react
Values are in the logarithmic scale. Use the following
formula to convert to percent:
9
0,5
MinLevel
8
Minimum brightness that can be set.
Value range: 0 - 254
Values are in the logarithmic scale. Use the following
formula to convert to percent:
10
0,5
MaxLevel
8
Maximum brightness that can be set.
Value range: 0 - 254
Values are in the logarithmic scale. Use the following
formula to convert to percent:
10
0,5
PhysicalMinLevel
8
Physical minimum brightness that a light source can
50