Such configured block has 3 outputs, each corresponding to one register. A value entered to a
given register will be sent from each output when values are entered
to the “observed”
register.
➢
The incoming data should be fed to the input of the
VERTEX Action
block configured in the
direct brightness control mode.
➢
After configuring the block controlling the here groups, we have the following control logic
diagram:
➢
After the changes are confirmed by pressing the
Deploy
button, the configuration runs
according to the assumptions. To get the brightness control in group GR 1, enter to register 0
a value from the 0
– 100 range. For groups GR 2 and GR 3, these are registers 10 and 20,
respectively.
REGISTERS FOR STORING INFORMATION ABOUT GROUPS
The
Analog Output Holding Registers
memory bank is used to store information about the correct
status of the groups.
The group state are assigned to the registers in the memory bank by means of
VERTEX modbus out
block in the NodeRed application. The state of current groups is available using the
VERTEX
feedback
block.