System malfunctions
Fault codes for the NRR 2-60 / NRR 2-61 level controller,
LRR 1-60 conductivity controller and URW 60 universal converter
Fault code
Internal
designation
Possible faults
Remedy
E.001
-
-
-
E.002
-
-
-
E.003
-
-
-
E.004
PlausSwitchpointErr
MIN switchpoint higher
than MAX switchpoint
Reset the switchpoints
E.005
InitTestErr
Internal error
Reboot the device and replace if necessary
E.006
WalkThroughAppErr
Internal error
Reboot the device and replace if necessary
E.007
WalkThroughTestErr Internal error
Reboot the device and replace if necessary
E.008
PlausSteamErr
Implausible measuring
range settings
Steam flowrate:
Min > Max
Check/reset steam flowrate
measuring range
E.009
PlausWaterErr
Implausible measuring
range settings
Feedwater flowrate:
Min > Max
Check/reset feedwater flowrate
measuring range
E.010
PlausPotiErr
Implausible calibration
points
Valve:
CLOSED (0 %) > OPEN
(100 %)
Check Valve CLOSED (0 %) and
Valve OPEN (100 %) calibration points
E.011
PlausErr
Implausible measuring
range settings
Min > Max
Check/reset measuring range
E.012
ProbeCommErr
Breakdown in communica-
tion with electrode
Check baud rate, group number, wiring and
terminating resistors
E.013
OvertempErr
Ambient temperature of
electrode > 75 °C
Check electrode installation location
Reduce ambient temperature of electrode
terminal box