39
URB 60 - Installation & Operating Manual -
819699-00
System information
Open the “
System Information
” menu
and select the desired action.
Description of display:
■
■
Startup
View a list of the last ten device restarts (e.g.
due to power failure), with the date and time.
■
■
Login
View a list of the last ten device logins with
date, time and password status.
PWL0 = failed login
PWL1/2 = successful login
■
■
Datalogs/Alarms
Save the data logs and alarm list to a USB
stick.
The file timestamps are in the
Unix time
stamp format
and can be counted back using
Excel formulae:
=DATE(1970;1;1)+(LINKS([CELL];10)/86400)
.
■
■
Error memory
Export the internal error log of selected CAN
bus nodes to a USB stick. To do this, you can
switch the desired devices in the lists on/off
and select them.
The data export („Reading“) takes
approx. 6 minutes per device.
■
■
Firmware Vx.x
Updates provided by GESTRA can be copied
onto the device using a USB stick.
1.
To do so, insert the USB stick in the device
and reboot the device.
This makes sure the USB stick is detected.
2.
Now perform the update.
■
■
PLC
Status display of the URB software.
■
◆
Run = OK
■
◆
Stop = error
“PLC Reset” followed by “PLC Start” com-
pletely deletes all internal parameters.
In the event of an error, please contact
GESTRA Service.