Configuring the level controller
Open the parameter screen.
Example: NRR 2-61 level controller
Description of parameters:
■
■
Controller
Displays the connected level controller and
its status:
■
◆
OK
The level controller is functioning without
problem.
■
◆
Offline
No communication with the URB 60.
■
◆
Collective fault
A fault has occurred in the level controller.
■
◆
Alarm
Value above or below limit.
■
■
Electrode
Displays the level electrode in question, and
its status. For status messages, see controller.
■
■
Xw = control deviation
Control deviation = actual value X - setpoint W
■
■
Max1 *
Set the Max. limit for the boiler level in percent.
■
■
Setpoint
Set the desired setpoint.
■
■
Min1 *
Set the Min. limit for the boiler level in percent.
If the “Max1/Min1” limits are reached, the
parameter row changes colour.
* You can test the relays of the
connected level controller if necessary,
see following page.
Description of pump icons (P1/P2)
The pump icons are displayed dynamically based
on the set number of pumps (1 or 2).
Green = pump on
White = pump off
Only one pump at a time can be in operation.
Description of bar charts:
X = actual value (compensated)
X1 = actual value (uncompensated),
see page 47, 3C controller
(not shown here)
W = setpoint
Yw = control point