48
URB 60 - Installation & Operating Manual -
819699-00
Configuring the conductivity controller
Open the parameter screen.
Example
Description of parameters:
■
■
Controller
Displays the connected conductivity controller
and its status:
■
◆
OK
The conductivity controller is functioning
without problem.
■
◆
Offline
No communication with the URB 60.
■
◆
Collective fault
A fault has occurred in the conductivity
controller.
■
◆
Alarm
Value above or below limit.
■
■
Electrode
Displays the conductivity electrode in ques-
tion, and its status. For status messages, see
controller.
■
■
Max
Set the Max switchpoint.
■
■
W
Set the setpoint.
■
■
Min
Set the Min switchpoint.
If the “Max/Min” switchpoints are reached,
the parameter row changes colour.
You can change the unit between
“µS/cm” and “ppm” if required, see
page 37, Device settings.
Display for configuring
Description of bar charts:
X = actual value
W = setpoint
Yw = control point in % based on the
continuous blowdown valve stroke
“Intermittent blowdown”
If the
Min
contact of the LRR 1-60 conductivity
controller was configured as
“Intermittent blowdown” (see page 52), the
display changes and the time until the next blow-
down is shown.