Configuring the level controller
Setting the level controller for 3-component control
The 3C controller icon appears only if
a controller of this type is used in the
system.
Open the 3C control
parameter screen.
Description of parameters:
■
■
Feedwater flowrate
■
■
Steam flowrate
For each type of flowrate, enter the measuring
range of the connected sensors
under the analogue signal inputs
(4 mA / 20 mA).
■
■
Quality factor (“Evaluation factor”)
This factor assesses how much the differ-
ence (steam flowrate - feedwater flowrate)
influences the measured level.
Description of bar charts:
X = actual value (compensated)
X1 = actual value (uncompensated)
Yw = control point
Controlled actual value = level - (steam flowrate - feedwater flowrate) x quality factor.
(Only if steam flowrate - feedwater flowrate > 0)
.