31
1. To enter or change the node ID, select the
green input field. The standard factory setting
is 41. When using more than one NRG 26-40,
a different node ID must be set here and in
the electrode.
2. Use the button
Node On/Off
to activate or
deactivate the input.
3. To name the CAN inputs, select the green
input field.
4. In the input mask, the on-screen keyboard
can be used to enter or change the name.
5. To change the limit values, select the relevant
input field.
6. In the input mask, the on-screen keyboard can be used to enter or change the value.
CAN 1...10 input NRG 2640
1. Select a green input field in the menu of the CAN inputs.
2. If a CAN input is already parametrised, a
relevant status screen like this is shown;
in this example, the capacitive level electrode
NRG 26-40.
3. The setup menu is password protected.
Press
and enter your password.
4. To get to the following setup menu, press the
button
.
Menus of Inputs/Outputs
continued
Note
The settings for the HiHi and LoLo values can be used for alarms and the Hi and Lo val-
ues can be used for switchpoints of 2-position controllers. All limit values can be used as
input parameters in the menu “Logical links”. It is also possible to control digital outputs
with the limit values entered here.
If all values from HiHi to LoLo are set to 0, limit value monitoring is deactivated.
If HiHi/LoLo alarms are switched off, no entry is made in the alarm log.
CAN 1...10 input NRG 2640 setup