59
Controller Menus
continued
3element continuous controller setup
1. Press the button
Cont. controller
in the menu
3element contr. setup
.
2. The name of the controller is
highlighted in yellow.
3. The green input fields
Qty. of steam, Water
flowrate
and
Level
show the signals that
have been set. Select the input field to show
all established signals.
4. Select the signal that is to provide the
measured value.
5. The green input field
Rating
shows the
value that has been set. To change this,
select the input field. The value rates the
influence of the difference (steam and water
flowrate) on the measured level signal.
6. The current value appears in the input mask.
The on-screen keyboard can be used to modify this.
7. To toggle the setpoint between Internal and External, press the button
Internal setpoint /
External setpoint
.
8. To enter a signal for an external setpoint, select the green input field. All established sensing ele-
ments will be indicated.
9. The green input field
Position
shows the position indicator. To choose a signal to deliver the
position feedback signal, select the green input field. All signals that have been set may be se-
lected.
10. The green input field
Manip. variable
shows the manipulated variable element. To choose a sig-
nal for the manipulated variable, select the green input field. All signals that have been set may
be selected.
11. The green input field
Offset
displays the current value. To change the value, select the input field.
12. The green input fields
Limit min/max
show the current limit values for the manipulated variable.
Select the relevant input field to enter or change the value.
13. The green input field
Deadz. min/max
indicates an actual value zone of the controller where the
controller delivers an unaltered manipulated variable. To enter or change the value, select the
input field.
Note
Controlled actual value = Level – (Qty. of steam – water flowrate) x Rating (only when
Qty. of steam – Water flowrate > 0).
If the signal for steam quantity or water flowrate is faulty, the controller will only use the
Level actual value.
Содержание SPECTORcontrol
Страница 82: ...82 For your notes ...
Страница 83: ...83 For your notes ...