77
Systematic malfunction analysis
In system malfunctions in a CAN bus system with several bus participants, the source of an error must
be systematically analysed, as individual faulty components or incorrect settings can cause negative
interactions between bus participants in CAN bus systems. Error messages may appear for fully func-
tional bus participants as a result of these negative interactions, which makes it difficult to localise the
error(s).
We recommend the following system during malfunction analysis:
System Malfunctions
Step 1 (start)
Remove terminal strips
in all bus participant
sensors.
Level electrode
Conductivity electrode
Pressure sensor
Temperature sensor,
etc.
Step 3
Switch on power
supply for the bus
participants of the
system
for example
NRS ...
and
NRG ...
Step 2
Attach the terminal
strips of the sensor
for a system,
for example
NRS ...
and NRG ...
(electrodes).
System OK
Remove the terminal
strips between the
bus participants in
the system,
for example
NRS ...
and
NRG ....
System error
Identify the error using
the error checklists.
Disconnect the device
from the power supply.
Test
Rectify the error using
the error checklists.
Final check − have all
errors been rectified?
Check the next system
Содержание SPECTORcontrol