Internal logical links 1...10 setup
Boiler Menus
continued
1. The menu
Logical links setup
is password
protected.
Press
and enter your password.
2. Select the green input field
Name
and enter
a name for the link.
3. Select the link symbol to adjust the desired
function.
The following options are available:
– AND
– OR
– SET / RESET (flip-flop)
4. Select the time symbol and set the desired
time properties.
The following options are available:
– Time off No time
(no time input field visible)
– TON
Startup delay
(time can be set in input field)
– TOF
Shutdown delay
(time can be set in input field)
– TP
Pulse
(time can be set in the input field)
5. Select the green input field at the input of the link.
Select the desired signal:
– CAN input (HiHi; Hi; Lo, LoLo)
– Analogue input
(HiHi; Hi; Lo, LoLo)
– Digital input
(parametrised dig. inputs)
– Internal log. link
(output of a parametrised log. link)
6. Select the buttons on the inputs or on the output of the link symbol to determine whether the
signal is to be processed directly or negated.
directly
negated
Note
The signal status
ON
is shown by red connecting lines.
The combination status
ON
is shown by the yellow signal lamp at the output of the link.
Log. links can be used in enabling controllers and in digital outputs and can also be
combined with each other.