13
Commissioning
continued
CAN bus connection
The connection to the CANopen equipment is implemented via the CAN interface.
A D-subminiature plug connector (in accordance with DIN 41652) must be used for the connection
cable. Use a multi-core flexible control cable as the supply line.
Note that a screened multi-core twisted-pair control cable is required as a bus line, e.g. UNITRONIC
®
BUS CAN 2 x 2 x...mm
2
or RE-2YCYV-fl 2 x 2 x...mm
2
.
Cable length
Number of pairs and conductor size [mm
2
]
125 m
2 x 2 x 0.34
250 m
2 x 2 x 0.5
335 m
2 x 2 x 0.75
500 m
available on demand (depends on bus configuration)
1000 m
1000 m
Note
The design and preparation of the data cable is an important factor for the electromag-
netic compatibility (EMC) of SPECTOR
control
. Connection should therefore be carried out
with special care (see equipment specification of the display and operating panel CPC-,
EP- or XV-XXX).
UNITRONIC
®
is a registered trademark of LAPP Kabelwerke GmbH, Stuttgart.