62
Controller Menus
continued
Intermittent blowdown
1. Press the button
in the menu
Controller
.
2. The menu
Intermittent blowdown
is
password protected.
Press
and enter your password.
3. The field
Valve status
shows the name of
the digital output. If the output is activated,
the background colour changes from yellow
to green.
4. The yellow numeric fields show the currently
remaining run times. When the pulse interval
has elapsed, the intermittent blowdown valve
opens for the specified amount of time. The
number for the intermittent blowdown pulse
and the intermittent blowdown interval are
also shown as remaining run time.
5. Select
for parametrisation.
6. Press the button
Manual
to manually start the intermittent blowdown process.
The pulse interval time is restarted.
Blowdown setup
1. Press the button
in the menu
Intermittent blowdown
.
2. The green input field
Signal assignment
shows the name of the signal output to be
activated. Select the green input field to
show all established signals.
3. Enter the values in the fields
Blowdown
duration
(recommended 2-3 s),
Pulse in
terval
,
Blowdown interval and Blowdown
frequency
. To do this, select the green input
field.
4. The green input field
Block signal
shows the
name of the input signal that prevents the
intermittent blowdown process.
Select the green input field to show all estab-
lished signals.
5. The
Block delay
indicates a time after which the intermittent blowdown is re-enabled after the
block signal has become inactive.