50
Controller Menus
continued
Continuous controller setup
continued
Note
The min. and max. limit values specify the manipulated variables of the controller.
The deadzone can be set in the +/- 10 % ranges. If the actual value is in the setpoint’s
+/- deadzone, the manipulated variable of the controller is stopped. The deadzone refer-
ence/standardisation relates to the set measurement range of the actual value.
Continuous controller softstart
1. Press the button Softstart on/off, to activate/deactivate the softstart.
2. To change the limit value, select the green input field.
3. The current value appears in the input mask.
The on-screen keyboard can be used to enter
or modify this text.
4. To change the gradient, select the green input
field.
Note
The limit value is the setpoint – the actual value. If the value is below this level, the soft-
start is automatically activated and drives the setpoint to the set gradient. This happens
if:
– the system is restarted
– the system is toggled from automatic -> manual
– the controller has been enabled
The softstart switches off when the value no longer falls below the set limit value. The
status of the softstart is provided automatically in the controller parameters at the top
right of the screen.