489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
CG.3.8 Memory Map Data Formats
The data formats used in the Modbus memory map are shown below.
302A
Hottest Other RTD Temperature
–50 to 250
1
°C
F4
0
302B
Hottest Ambient RTD Number
1 to 12
1
–
F1
1
302C
Hottest Ambient RTD Temperature
–50 to 250
1
°C
F4
0
302D
Analog Input 1
–50000 to 50000
1
Units
F12
0
302F
Analog Input 2
–50000 to 50000
1
Units
F12
0
3031
Analog Input 3
–50000 to 50000
1
Units
F12
0
3033
Analog Input 4
–50000 to 50000
1
Units
F12
0
3035
Phase A Neutral Current
0 to 999999
1
Amps
F12
0
3037
Phase B Neutral Current
0 to 999999
1
Amps
F12
0
3039
Phase C Neutral Current
0 to 999999
1
Amps
F12
0
30E0
Hottest Stator RTD Temperature
–50 to 250
1
°F
F4
0
30E1
Hottest Bearing RTD Temperature
–50 to 250
1
°F
F4
0
30E2
Hottest Other RTD Temperature
–50 to 250
1
°F
F4
0
30E3
Hottest Ambient RTD Temperature
–50 to 250
1
°F
F4
0
30E5
Neutral Voltage (Fundamental)
0 to 250000
1
Volts
F10
0
30E7
Neutral Voltage (3rd Harmonic)
0 to 250000
1
Volts
F10
0
30E9
Vab/Iab
0 to 65535
1
ohms s
F1
0
30EA
Vab/Iab Angle
0 to 359
1
°
F1
0
WAVEFORM MEMORY SETUP
30F0
Waveform Memory Trigger Date
N/A
N/A
N/A
F18
N/A
30F2
Waveform Memory Trigger Time
N/A
N/A
N/A
F19
N/A
30F4
Frequency During Trace Acquisition
0 to 12000
1
Hz
F3
0
30F5
Waveform Memory Channel Selector (Holding Register)
0 to 9
1
N/A
F214
0
30F6
Waveform Trigger Selector
1 to 65535
1
N/A
F1
0
30F7
Waveform Trigger Cause (Read-only)
0 to 139
1
N/A
F134
0
30F8
Number of Samples per Trace
1 to 1536
-
-
F1
N/A
30F9
Number of Waveform Captures Taken
0 to 65535
1
N/A
F1
0
WAVEFORM MEMORY SAMPLES
3100
First Waveform Memory Sample
–32767 to 32767
1
-
F4
0
3700
Last Waveform Memory Sample
–32767 to 32767
1
-
F4
0
*. A Value of 65535 indicates ‘Never’
. A value of 0xFFFF indicates “no measurable value”.
. Maximum value turns feature ‘Off’
Table CG–1: 489 Memory Map (Sheet 30 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42
Table CG–2: Data Formats (Sheet 1 of 14)
CODE
TYPE
DEFINITION
F1
16 bits
UNSIGNED VALUE
Example: 1234 stored as 1234
F2
16 bits
UNSIGNED VALUE,
1 DECIMAL PLACE
Example: 123.4 stored as 1234
F3
16 bits
UNSIGNED VALUE,
2 DECIMAL PLACES
Example: 12.34 stored as 1234
F4
16 bits
2’s COMPLEMENT SIGNED VALUE
Example: –1234 stored as –1234 (i.e. 64302)