489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
69
60
F1
Ground Current Scale Factor. Will always be a
power of 10 (1, 10, 100, etc.). Changes only when
the configuration setpoints are changed.
Class 1
Note 3
61
F3
Ground Current (scaled according to the previous
point)
Class 2
62
F1
Phase A-B Voltage
Class 2
63
F1
Phase B-C Voltage
Class 2
64
F1
Phase C-A Voltage
Class 2
65
F1
Average Line Voltage
Class 2
66
F1
Phase A-N Voltage
Class 2
67
F1
Phase B-N Voltage
Class 2
68
F1
Phase C-N Voltage
Class 2
69
F1
Average Phase Voltage
Class 2
70
F3
Per Unit Measurement Of V/Hz
Class 2
71
F3
Frequency
Class 2
Note 2
72
F1
Fundamental Frequency Neutral Voltage (volts)
Class 2
Note 10
73
F10
Fundamental Frequency Neutral Voltage (tenths of
a volt)
Class 2
Note 10
74
F1
Third Harmonic Neutral Voltage (volts)
Class 2
Note 10
75
F10
Third Harmonic Neutral Voltage (tenths of a volt)
Class 2
Note 10
76
F1
Third Harmonic Terminal Voltage (volts)
Class 2
Note 10
77
F10
Third Harmonic Terminal Voltage (tenths of a volt)
Class 2
Note 10
78
F2
Vab/Iab (loss of excitation impedance)
Class 2
79
F1
Vab/Iab Angle (loss of excitation impedance angle)
Class 2
80
F6
Power Factor
Class 2
81
F1
Real Power (MW)
Class 2
Note 8
82
F1
Real Power (kW)
Class 2
Note 8
83
F1
Reactive Power (Mar)
Class 2
Note 8
84
F1
Reactive Power (kvar)
Class 2
Note 8
85
F1
Apparent Power (MVA)
Class 2
Note 8
86
F1
Apparent Power (kVA)
Class 2
Note 8
87
F1
Hottest Stator RTD
Class 2
Note 3
88
F4
Hottest Stator RTD Temperature (°C)
Class 2
89
F4
RTD #1 Temperature (°C)
Class 2
90
F4
RTD #2 Temperature (°C)
Class 2
91
F4
RTD #3 Temperature (°C)
Class 2
Table CG–8: Analog Inputs Point List (Sheet 3 of 5)