489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
19
LEARNED DATA / PARAMETER AVERAGES
0600
Average Generator Load
0 to 2000
1
%FLA
F1
0
0601
Average Negative Sequence Current
0 to 2000
1
%FLA
F1
0
0602
Average Phase-Phase Voltage
0 to 50000
1
V
F1
0
0603
Reserved
–
–
–
–
–
0604
Reserved
–
–
–
–
–
LEARNED DATA / RTD MAXIMUMS
0620
RTD #1 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0621
RTD #2 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0622
RTD #3 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0623
RTD #4 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0624
RTD #5 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0625
RTD #6 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0626
RTD #7 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0627
RTD #8 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0628
RTD #9 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0629
RTD #10 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
062A
RTD #11 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
062B
RTD #12 Maximum Temperature (Celsius)
–52 to 251
1
°C
F4
–52
0640
RTD #1 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0641
RTD #2 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0642
RTD #3 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0643
RTD #4 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0644
RTD #5 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0645
RTD #6 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0646
RTD #7 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0647
RTD #8 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0648
RTD #9 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
0649
RTD #10 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
064A
RTD #11 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
064B
RTD #12 Maximum Temperature (Fahrenheit)
–52 to 251
1
°F
F4
–52
489 MODEL INFORMATION
0650
Relay serial number (read only)
N/A
1
---
F22
A3000000
↓
↓
↓
↓
↓
↓
↓
0653
Relay serial number (read only)
N/A
1
---
F22
A3000000
COMMUNICATION ACTUAL VALUES
0660
CoBox serial number
---
---
---
F22
---
0674
CoBox MAC address
---
---
---
F22
---
0688
CoBox firmware version
---
---
---
F22
---
069C
Ethernet status
---
---
---
F152
---
LEARNED DATA / ANALOG IN MIN/MAX
0700
Analog Input 1 Minimum
–50000 to 50000
1
Units
F12
0
0702
Analog Input 1 Maximum
–50000 to 50000
1
Units
F12
0
0704
Analog Input 2 Minimum
–50000 to 50000
1
Units
F12
0
0706
Analog Input 2 Maximum
–50000 to 50000
1
Units
F12
0
0708
Analog Input 3 Minimum
–50000 to 50000
1
Units
F12
0
070A
Analog Input 3 Maximum
–50000 to 50000
1
Units
F12
0
070C
Analog Input 4 Minimum
–50000 to 50000
1
Units
F12
0
070E
Analog Input 4 Maximum
–50000 to 50000
1
Units
F12
0
MAINTENANCE / TRIP COUNTERS
077F
Trip Counters Last Cleared (Date)
N/A
N/A
N/A
F18
N/A
0781
Total Number of Trips
0 to 50000
1
–
F1
0
0782
Digital Input Trips
0 to 50000
1
–
F1
0
Table CG–1: 489 Memory Map (Sheet 7 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42